Outside Air Economizers & Stuck Dampers: Hidden Energy Failures
- Alex Khachaturian

- Sep 15
- 6 min read

One-line promise: Find and fix the silent energy leaks in your AHUs, fast. This is your field-ready playbook for diagnosing outside air economizers and stuck dampers without guesswork.
(Subscribe for field-tested guides like this, free. New posts every Tue/Thu/Sat.)
TL;DR
If your economizer is misconfigured or the OA damper is stuck, you’re paying to heat/cool the outdoors.
A 60-second temp check (RA/MA/OA) reveals 80% of economizer issues.
Trend it, test it, tighten it: verify sequences, free the hardware, and lock in changeover logic.
Key Takeaways
Economizers are free cooling when outdoor air is better than return air. If the logic or hardware is wrong, they become free losses.
Stuck dampers and failed actuators are more common than bad logic, but bad logic costs more because it runs every day.
Three temps (OA/RA/MA) + one trend chart turn “mystery” into “math.”
Commissioning beats repair. Once you dial it in, lock it down with alarms, trends, and accountability.
A Quick Story
I walked into a “high-efficiency” building that couldn’t keep a stable lobby temp. Energy bills were creeping up, and the facilities team swore the system was “fine.” Schedules looked right, PID loops were calm, and the BAS graphics were clean. But walking the air handler told a different story.
Return air was cozy. Outside air was crisp. Mixed air? Somehow hotter than return.
The outside air damper’s crank arm looked aligned on the graphic… but the real damper blade was frozen mid-position by a seized linkage arm. The actuator was doing bicep curls on a steel statue. The economizer sequence was also set to enthalpy changeover, but the sensor had drifted years ago.
We freed the damper, replaced a $120 sensor, corrected the changeover logic, and added three trend logs. The next month’s bill? Down. Comfort complaints? Gone.
That’s the game with outside air economizers: they’re either your best friend… or your biggest invisible energy failure.
Quick Win: 60-Second Economizer Test
When the unit’s running:
Measure OA, RA, and MA dry-bulb temps (probes > IR).
Sanity check the sequence: If OA is cooler than RA by ~3–5°F (and dry), your economizer should open. MA should shift toward OA.
If MA ≈ RA while the BAS says OA damper is “open,” you likely have a mechanical issue (linkage, blade, actuator).
If MA tracks OA correctly but comfort/energy is bad, suspect changeover logic, setpoints, or sensor calibration.
Rule of thumb: MA should move when OA damper position changes. If the number doesn’t move, neither does your savings.
Step-by-Step Playbook
1) Outside Air Economizers: What They Are and Why They Fail
Outside air economizers bring in more outdoor air when it’s cooler (or lower enthalpy) than return air, delivering “free cooling.” Fail modes:
Stuck or binding damper blades
Slipped linkages or loose set screws
Weak or failed actuators
Sensor drift (OA, RA, MA, enthalpy)
Bad changeover (wrong DB/enthalpy thresholds)
Overrides left on after service
Minimum OA not actually minimum (blades misindexed)
2) Confirm the Sequence (before tools)
Pull the actual written sequence or controller app. Answer:
Changeover type? (Dry-bulb, enthalpy, or both)
Minimum OA setpoint? (10%? 20%? As-built?)
Alarm logic? (No movement? Sensor fault?)
Freeze/smoke lockouts correct?
Supply/space humidity limits in play?
If you can’t find it, write it. Bad or missing sequences guarantee bad outcomes.
3) Three-Temperature Method
Measure OA/RA/MA. Compare to commanded OA damper position.
If OA < RA (by ~3–5°F) and dry, economizer should open → MA should shift toward OA.
If MA doesn’t budge, mechanical problem.
If MA moves but schedule/comfort still wrong, logic or calibration problem.
4) Mechanical Inspection (hands and eyes)
Pop the access panel. Watch the damper while commanding open/close.
Check blade bearings for corrosion or debris.
Verify actuator torque rating and stroke.
Tighten/linkage set screws; replace egged-out couplers.
Lube sparingly (silicone) if manufacturer allows.
Confirm end-stops: don’t let the actuator fight steel.
5) Sensor Health & Calibration
Compare OA sensor to a trusted handheld; same for RA and MA.
Replace drifty sensors; don’t “math” your way around a liar.
If using enthalpy changeover: verify dry-bulb and RH sources.
Label the sensors on-site. Future teams shouldn’t have to play “Where’s Waldo.”
6) Changeover Logic That Actually Saves
Dry-bulb works in dry/cool climates.
Enthalpy protects you in humid regions; dry-bulb alone will trick you on muggy days.
Set realistic thresholds and hysteresis to avoid damper hunting.
Respect supply air temperature limits (don’t flood coils with cold OA and freeze).
7) Minimum OA That’s Truly Minimum
Commission minimum via measured airflow (hood, traverse, or DP + K-factor), not guesswork.
Mark blade index position for “true minimum.”
Trend MA temp and supply fan kW; minimum that’s too high wastes money every hour.
8) Prove It With Trends
Trend for at least a week:
OA/RA/MA temps (and RH if enthalpy)
OA damper command vs. feedback
SAT, fan status, freeze stat trips
Space CO₂ (if DCV)Overlay weather data. You want to see changeover happen at the right moments and MA respond accordingly.
9) Lock It In
Add alarms: “Commanded open, MA unchanged” and “Sensor out of range.”
Add a post-PM checklist item: cycle OA damper, capture photos, confirm trends.
Document the final settings and store in the digital O&M.
Troubleshooting (Symptom → Cause → Fix)
MA temp doesn’t change when OA damper “opens.”→ Stuck blades, dead actuator, broken linkage.→ Fix: Free/replace hardware; add position feedback and alarm.
Unit short-cycles on freeze protection during “free cooling.”→ OA too cold, no SAT limit, minimum too high.→ Fix: Add SAT low limit, reduce minimum OA, stage mixing.
Spaces feel humid during economizer.→ Dry-bulb changeover in a humid climate; enthalpy sensor drift.→ Fix: Switch to enthalpy or dual changeover; recalibrate sensors.
High CO₂ even with “OA open.”→ Damper commanded but not moving; minimum OA set too low; sensor location poor.→ Fix: Repair damper; set minimum by measurement; relocate CO₂ sensor.
Energy bills up after “energy project.”→ Minimum OA mis-set, sensor drift, overrides left on.→ Fix: Re-commission minimum and changeover; clear overrides; trend and verify.
BAS says 25% OA, but it looks closed.→ Graphic scaling wrong; no feedback; linkage slipped.→ Fix: Add/validate position feedback; rescale; tighten linkage.
FAQ
How often should I test my economizers?
At least seasonally and after any controls or PM work. Add a quick OA/RA/MA check to every filter change.
Dry-bulb or enthalpy, what’s better?
Depends on climate. Humid climates benefit from enthalpy changeover. In arid regions, dry-bulb performs well.
What’s a good minimum OA?
Start from design/ventilation code needs, then measure with a hood/traverse. “10% on the graphic” is not a measurement.
Do I need position feedback on OA dampers?
Yes. It turns guesswork into diagnostics and enables “commanded vs. actual” alarms.
What’s the cheapest way to catch failures early?
A weekly trend review and a handheld thermometer. Fancy comes later, discipline wins now.
Can I trust IR guns for RA/OA/MA?
Not for air temps. Use probes. IR is fine for surface checks, not moving air.
Field Checklist
Pull sequence; confirm changeover logic and limits
Measure OA/RA/MA temps; compare to damper command
Watch the blades while commanding movement
Verify actuator torque/stroke; tighten linkages; set end-stops
Calibrate/replace OA/RA/MA (and RH) sensors
Commission minimum OA by measurement
Add trends: temps, RH (if used), damper cmd/feedback, SAT
Add alarms for “no movement” and “sensor out of range”
Document settings; attach photos; schedule seasonal checks
Results & ROI (Show the Dollars)
Small numbers, big bills:
Extra unneeded 1,000 CFM of OA (minimum set too high) at a 30°F winter delta adds:
BTU/hr = 1.08 × 1,000 × 30 = 32,400 BTU/hr ≈ 9.5 kW
Run that 1,000 hours and you burn ~9,500 kWh. At $0.12/kWh, that’s ~$1,140 for one unit, one season.
A single stuck-open OA damper on a 10,000 CFM AHU can quietly wipe out the savings of your entire “LED retrofit.” Economizers multiply impact because they run daily.
Typical tune/repair kit (actuator + sensor + 2 hours labor) often pays back in 1–3 months on medium AHUs. On large AHUs, sometimes one billing cycle.
Bottom line: The math favors the tech who measures.
Wrap-Up
Economizers should feel like cheating, in your favor. When OA is better than RA, bring it in and ride the free cooling. When it isn’t, shut the gate. Everything in this article, three temps, a watchful eye, measured minimums, honest sensors, protects that simple truth. Do the boring parts right, and you’ll get fewer complaints, calmer graphs, and lower bills.








Comments